ACB Retrofit & LV Switchboard Modernisation

Case Study

Petrofac – Kittiwake Platform

We delivered a major switchgear obsolescence and reliability improvement programme for Petrofac’s Kittiwake platform, comprising both low-voltage cubicle retrofits and air circuit breaker (ACB) modernisation across multiple critical switchboards. The project was engineered to address ageing equipment, overheating issues, and component obsolescence while extending the operational life of the existing switchgear infrastructure.

Project Highlights

🔹Completed 20 LV cubicle retrofit upgrades across three 440V switchboards, replacing ageing motor starters, contactor feeders and fused switch units.

🔹Designed, manufactured and commissioned bespoke replacement cubicles to resolve overheating issues and improve long-term equipment reliability.

🔹Upgraded DOL motor starters ranging from 0.55kW to 45kW, including earth fault protection, motor protection and metering where required.

🔹Replaced contactor feeders and fused switch feeders rated up to 100A, utilising modern Schneider, Socomec and Hobut components.

🔹Manufactured bespoke pre‑wired doors and backplates for seamless installation

Image above shows some of the completed kits trial fitted into an unused S&I switchboard at our factory in Norwich.

🔹Completed 15 ACB retrofit upgrades across four switchboards, replacing obsolete Terasaki AP and AH series breakers with modern Terasaki TemPower2 AR withdrawable ACBs.

🔹Installed new ACB retrofit assemblies rated from 1600A to 3200A, including engineered hard bus retrofit housings, bespoke copper busbar connections and custom modification kits.

🔹Integrated modern protection and control functions, including overcurrent, earth fault, auxiliary indication, position monitoring, Castell safety interlocking and remote umbilical switching functionality.

🔹Undertook offshore installation, testing and commissioning, delivering a fully operational solution with minimal disruption to platform operations.

All works were delivered through a mix of factory‑built retrofit kits and on‑site installation, testing, and commissioning.

Images above show before and after installation.


Client Benefits

🔹Extended service life of critical switchgear assets without full board replacement.

🔹Improved system reliability through the elimination of obsolete and overheating equipment.

🔹Enhanced personnel safety through modern protection, and remote switching functionality.

🔹Increased maintainability through standardised components and simplified future spares support.

🔹Reduced operational risk by upgrading essential power distribution and motor control systems whilst retaining the existing switchboard infrastructure.